Product Specifications
(New Formula)
The Original Liquid Dehydrant for Control of
Moisture in Refrigeration Systems.
When THAWZONE is added directly to the refrigerant
of a system it will mix and circulate with the refrigerant. It seeks out
moisture, chemically bonds to it and prevents freezing. THAWZONE contains
special ingredients that stabilize refrigerants, neutralize acids, dissolve
gum and the new formula helps oil return in low temperature systems. THAWZONE'S
primary purpose is to free frozen systems fast. When THAWZONE is added
to a frozen system the system will be back in service by the time the
refrigerant has cycled twice.
THAWZONE can be used with or without solid driers.
It does not have any effect on solid driers and solid driers do not affect
THAWZONE. Some THAWZONE is always absorbed on driers, the extent of adsorption
depends on the temperature and pressure of the system, as well as, the
desiccant present but in all cases water is preferentially adsorbed. THAWZONE
acts as a carrier in the system working with the desiccants it travels
through the system picking up any moisture and dripping that moisture
off for the desiccant to adsorb. A high quality desiccant used with THAWZONE
will quickly and permanently solve moisture and associated acid problems.
THAWZONE works when other solid driers fail because
it is not affected by the temperature of the system. When a system overloads
the refrigerant temperature increases and solid driers return part of
the moisture that they are holding to the system. This can cause intermittent
freezing of the system. THAWZONE prevents this problem because it holds
the moisture despite temperature.
THAWZONE is completely safe. It will not corrode
any parts of a refrigeration system and is usable in all types of equipment
large or small, open or hermetic and it is compatible with all refrigerants
including all CFC's, HFC's and HCFC's.
Highside System Injector is recommended for introducing
Thawzone into an operating system.
Recommendations for Charging
THAWZONE® To Refrigeration Systems
QUANTITY to Use: Add 1/8 fluid ounce (3.75 ml)
of THAWZONE directly to the refrigerant of any system for every 1 lb.
of refrigerant in the system.
- 1. If the system in large, THAWZONE can be
added by using a standard oil charging pump; (add directly to refrigerant
not to crank case.)
- 2. If the system is small, place the proper
amount of THAWZONE in a charging hose and connect one end to the low-side
access valve on the compressor and the other end to a source of refrigerant.
A 36" charging hose holds 22ml OR 3/4 OF A FLUID OUNCE. Purge both ends
of the hose and tighten fittings. Open the valve at the refrigerant
source. Now with the source of refrigerant above the access valve, crack
the access valve very slowly and force THAWZONE into the system with
refrigerant. CAUTION: THAWZONE is a liquid and will sludge the compressor
if charged too quickly.
- 3. Make up a charging unit out of standard
pipe fittings. (1-2 X 1/2 nipple and 2- 1/4 male flare X1/2 female pipe).
Assemble flare fittings on both ends of the nipple. Place a proper amount
of THAWZONE in this unit. Using charging hoses, connect one end of the
unit to the access valve on the low-side of the compressor and the other
end to a source of refrigerant. Purge the system. Then make sure the
fittings at the access valve are not securely tightened and move the
source of refrigerant to a position above the access valve are securely
tightened and move the source of refrigerant to a position above the
access valve to that the line and charging unit slope down toward the
access valve. Very slowly crack the access valve on the the compressor
and force THAWZONE into the system with refrigerant.
Remember! THAWZONE is a liquid and will sludge the compressor if
charged too quickly.
|